  ev e nt input/output modul e [ pum e] pume is a digital input / output module used as an auxiliary input / output of control modules. each module, 30mm wide, is equipped with 8 points of digital input, 8 points of digital output, and high-speed rs-485 port. by connecting with pum control modules, it realizes a compact and high- performance system. fea tu res i. u ser-friendly structure and functions 1 . l ateral connection : max.16 units + control module 16 units = total 32 units s imple wiring for power supply and communication 2 . d etachable structure: terminal block, main unit, and the base part easy wiring with detachable terminal blcok main units exchangeable without re-wiring 3 . s tatus led for each input/output easy to monitor input / output status 4 . s mart loader communication: connect one module and all connected modules are able to communicate using a loader software. ii. l arge scale system using high speed rs-485 1 . m odbus rtu protocol for large volume communica- tion 2 . h igh-speed communication: maximum 115.2kbps 3 . h ighly-effcient communication: parameters dispersed on the address map are re-allocated to contiguous address iii. v arious functions to extend control module functions 1 . d igital input ( optional feature : logic operation not/and/or) < functions set by di function of control module> - run / standby switch - auto / remote / manual switch - start timer - others 2 . d igital output ( optional feature : logic operation not/and/or) - control output (including distribution output) - alarm output - timer output - others pum series multi-loop module type temperature controller pume data sheet EDS11-167A apr. 1, 2011 date sys t e m s p ec i f i ca tion 1. p roduct type: m ulti-loop module type temperature controller 2. m odule type 1) a nalog module: t otal maximum 16 units a) c ontrol module (4 loop/unit) b) e xtended input/output module - a nalog input/output module (input/output 4 points/unit) - a nalog input module (input 4 points/unit) - a nalog output module (output 4 points/unit) 2) e xtended input/output (digital) module: maximum 16 units - e vent input/output module (input/output ; 8 points/unit) 3) enhanced communication module: 1 unit 3. c onnecting method: lateral connecting with connectors - f or power supply and rs-485 communication, any one of connected modules is required to be connected. 4. n o. of loop, input/output 1) c ontrol loop: m ax. 64 2) n o.of input / output: di 128 points / do 128 points
pume 2 event input/output module specification 1. general speci cation (1) power supply: 24v dc ?0% (2) power consumption:  max. 3.2 w (135 ma) [when 24v dc is applied] (3) insulation resistance: 20m or more (500v dc) (4) withstand voltage: power supply ? digital input ? digital output ? communication terminal 1000v ac 1 min. others (digital input between blocks, digital output between blocks) 500v ac 1 min. (5) applied standards: ul, c-ul, ce marking, rohs directive [pending for ul, c-ul marking] 2. digital input (1) no. of input: 8 points (4 points/common ?2 blocks) (2) input type: voltage contact input, sink/source com- mon (bidirectional) (3) input rating: 24v dc, input impedance approx. 4.7k (4) input judgment: on judgment: 16 to 26.4v dc off judgment: 0 to 5v dc (5) input read cycle (min. pulse width): 200ms (6) insulation: functional insulation with internal cir- cuit (7) option: not/and/or logic operation, latch ac- tion 3. digital output (1) no. of output: 8 points (4 points/common ?2 blocks) (2) output type: select from a) and b) according to model type speci cation a) relay contact output - contact structure: spst contact - contact capacity: 220v ac / 30v dc, 1a - insulation: functional insulation with inter- nal circuit b) transisitor open collector (sink) output - rating: 24v dc, 100ma (residual voltage when power is on: 1.5v dc or less) - insulation: functional insulation with inter- nal circuit (3) option: control output/event output selection, not/and/or logic operation, latch ac- tion 4. communication function 4.1 rs-485 interface (1) communication standards: rs-485 compatible (2) no. of port: 1 port (3) communication, synchro method: two-wire, half-duplex, asynchronous cycle (4) communication speed: 9.6k, 19.2k, 38.4k, 115.2kbps (5) communication distance: 1km (38.4kbps or less), 250m (115.2kbps) (6) recommended cable: kpev-sb 0.5sq-equivalent (7) no. of connectable units: 33 units (master and slave) (32 units if any modules other than pum series are included in slaves.) (8) data format: data bit; 8, parity; even / odd / none (9) protocol: modbus rtu compatible (10) insulation: no insulation with loader communication port functional insulation with any other in- put / output 4.2 loader communication (rs-232c) interface (1) communication standards: rs-232c compatible (2) no. of port: 1 port (3) communication, synchro method: half-duplex, asynchronous cycle (4) communication speed: 19.2kbps ( xed) (5) data format: data bit 8, no parity (6) protocol: modbus rtu compatible (7) connection method: 2.5 diameter mini-plug / jack [on the front of the module] (common cable with pxg, pxh) (8) insulation: no insulation with rs-485 functional insulation with any other in- put / output 5. display, con guration 5.1 display (1) display: status display led (2 colors ?2 points + 16 points) (2) display contents: run/fault, rs-485 tx/rx, input ?8 points, output ?8 points 5.2 setting device (1) setting device: rotary sw ?1 [on the front of the module] (2) set contents: rs-485 station no. (station no.= setting value + 17) 6. power outage (1) impact of power outage: outage of 2ms or less ; no impact (2) operation after power outage: start from the rst step (cold start) (3) memory backup: nonvolatile memory (eeprom) no. of update ; 100,000 7. self diagnosis diagnosis method: program error monitoring by watch dog timer 8. structure (1) installation method: din rail mounting or mounting with m3 screws inside a cabinet (2) dimensions: 30 (w) ?100 (h) ?85 (d) mm (excluding terminal cover and projected part) (3) weight: approx. 200 g
3 (4) extrenal terminal - digital input / digital output: detachable terminal block (m3 screw ?20 terminals) - power supply connection: terminal block on the base part (m3 screw ?2 terminals) power is supplied via side connectors in case of lateral connecting. (max. 33 units) - rs-485 communication connection: terminal block on the base part (m3 screw ?3 terminals) rs-485 communication is connected via side connectors in case of lateral con- necting. - loader communication port: 2.5 diameter mini-plug / jack [on the front of the module] (5) case material: polyphenylene oxide ( ame retardant grade : ul94v-0 equiva- lent) (6) case color: case ; red terminal, base part ; black (7) protection - body: ip20 grade protection (ventilation slits on the top and the bot- tom of the body) - terminal: ip00 grade protection, terminal cover is available as an option 9. normal operating condition (1) ambient temperature*: -10 to 50? * ambient temperature?is the tempera- ture underneath the controller inside the equpiment or the cabinet where the controller is installed. (2) ambient humidity: 90% rh or less (non condensing) (3) vibration: 10 to 70hz, 9.8m/s 2 (1g) or less 10. transporting, storage condition (packing con- dition) (1) storage temperature: -20 to 60? (2) ambient humidity: 90%rh or less (no condensing) (3) vibration: 10 to 70hz, 9.8m/s 2 (1g) or less (4) shock: 294m/s 2 (30g) or less 11. packing list temperature controller: 1unit instruction manual: 1 copy 12. loader software (1) distribution medium: free download from fuji electric sys- tems hp (http://www. c-net.jp/eng/index. html) (2) recommended operating environment pc: dos/v (pc-at compatible) os: windows xp (operation confirmed in japanese / english) ram: 256m bytes or more free space on the hardware: 500m bytes or more display resolution: 1024 ?768 or over serial interface: rs-232c 1 port (without rs-232c, usb serial converter cable required) (3) connection with pum via loader interface on the front face of the module (special cable available from fuji is required) or via rs-485
pume 4 code symbols [event input/ouput module] [accessories] [table 1] insulation block diagram description 4 5 10 e c r a b < module type > event input/output module [di 8 points / do 8 points] < output type > transisitor open collector (sink) output relay contact output japanese english digit 45678 9 10 123 pum yy 10 digit 6 7 8 a a a a l 0 0 0 0 0 1 2 3 4 1 rs-485 terminating resistance din rail mounting end plate side conneting terminal cover (right & left 1 set) front face screw terminal cover loader connecting cable (rs-232c) 45678 123 pumz * digit description digit power di1 to 4 loader communication port di5 to 8 rs-485 communication port do1 to 4 do5 to 8 functional insulation (1000v ac) functional insulation (500v ac)
5 outline diagram (unit : mm) please keep the distance of 30mm from this instrument to radiate. [50mm is recommended] front terminal cover (option) (10) 30 100 50 6.1 1. 5 5 6 at mounting to the din rail (8) 85 din rail main unit (at attach/detach) (30) locking tab hole for screw mounting base part (main unit is detached) dimensions for screw mounting (30) 9?.2 2-m3 (100) 88.5?.2 (3) notice at the installation 30 or more 30 or more +0.2 +0.7 30 station loader terminal screw m3 terminal block (at attach/detach) hole for screw mounting terminal screw m3
pume 6 terminal connection diagram station loader 11 12 22 21 13 14 15 16 17 18 19 20 23 24 25 26 27 28 29 30 24 25 digital input 22 21 23 12 345 base part power + - 2 1 communication rs485 a(+) 3 sg 4 b(-) 5 24v dc 1 2 3 gnd rx tx loader interface plug (rs-232c) 2.5 3-pole miniature plug 24v dc di2 di1 di4 di3 29 30 27 26 28 di6 di5 di8 di7 24v dc digital output 14 15 12 11 13 transistor o.c. (sink) l 24v dc l l l do1 do2 do3 do4 com 1 to 4 digital input 5 to 8 1 to 4 relay do1 do2 do4 do3 com 14 15 12 11 13 digital output 19 20 17 18 transistor o.c. (sink) l 24v dc l l l do5 do6 do7 do8 com 5 to 8 relay do5 do6 do8 do7 com 16 19 20 17 18 16
7 operation parameter parameter (name) read/write date setting range factory default registor no. run/standby switch 0: run 1: standby 0 (run) 40021 digital input latch releases command 0: off 1: release latch 0 (off) 40022 digital output latch releases command 0: off 1: release latch 0 (off) 40023 communication parameter parameter (name) read/write date setting range factory default registor no. rs-485 parity setting 0: none 1: odd 2: even 0 (none) 40111 rs-485 response interval time 0 to 25 (?0ms) 1 40113 rs-485 communication permission 0: read only 1: read/write 1 (r/w) 40114 rs-485 communication speed 0: 9.6kbps 1: 19.2kbps 2: 38.4kbps 3: forbidden 4: 115.2kbps 1 (9.6kbps) 40115 enhanced communication module (pumc) connection 0: pumc not connected (rs485 enable) 1: pumc connected (rs485 disable) 040116 con guration parameter parameter (name) read/write date setting range factory default registor no. fault output set value 0: hold 1: off 0 (hold) 40260 standby output set value 0000 to ffff 0000 40268 standby mode setting 0: di=input value, do=standby output set value 1: di=all off, do=standby output set value 0 40270 led2 lamp allocation 0 to 2 1 40222
pume 8 di parameter parameter (name) read/write date setting range factory default registor no. di1 input option 0 to 15 (bit data : 0000 to 1111 ) bit0 : latch bit1 : not bit2 : and bit3 : or 0 (bit data 0000) 40701 di1 input logic operation and 0000 to 00ff 0000 40703 di1 input logic operation or 0000 to 00ff 0000 40704 di2 input option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0000) 40705 di2 input logic operation and 0000 to 00ff 0000 40707 di2 input logic operation or 0000 to 00ff 0000 40708 di3 input option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0000) 40709 di3 input logic operation and 0000 to 00ff 0000 40711 di3 input logic operation or 0000 to 00ff 0000 40712 di4 input option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0000) 40713 di4 input logic operation and 0000 to 00ff 0000 40715 di4 input logic operation or 0000 to 00ff 0000 40716 di5 input option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0000) 40717 di5 input logic operation and 0000 to 00ff 0000 40719 di5 input logic operation or 0000 to 00ff 0000 40720 di6 input option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0000) 40721 di6 input logic operation and 0000 to 00ff 0000 40723 di6 input logic operation or 0000 to 00ff 0000 40724 di7 input option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0000) 40725 di7 input logic operation and 0000 to 00ff 0000 40727 di7 input logic operation or 0000 to 00ff 0000 40728 di8 input option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0000) 40729 di8 input logic operation and 0000 to 00ff 0000 40731 di8 input logic operation or 0000 to 00ff 0000 40732
9 do parameter parameter (name) read/write date setting range factory default registor no. do1 output type 0: event output 1: control output 0 (event output) 40401 do1 master module st. no. 0 to 255 0 40402 do1 master module ch. no. 1 to 4 1 40403 do1 bit position 0000 to 00ff 0001 40404 do1 output option 0 to 15 (bit data : 0000 to 1111) bit0 : latch bit1 : not bit2 : and bit3 : or 0 (bit data 0000) 40405 do1 output logic operation and 0000 to 00ff 0000 40407 do1 output logic operation or 0000 to 00ff 0000 40408 do1 scaling base -100.0 to 100.0% 0.0 40409 do1 scaling span -100.0 to 100.0% 100.0 40410 do1 proportion cycle 1 to 120 sec. 30 40411 do1 lower limits 0.0 to 100.0% 0.0 40412 do1 upper limits 0.0 to 100.0% 100.0 40413 do1 limit type 0 to 3 0 40414 do2 output type 0: event output 1: control output 0 (event output) 40415 do2 master module st. no. 0 to 255 0 40416 do2 master module ch. no. 1 to 4 1 40417 do2 bit position 0000 to 00ff 0002 40418 do2 output option 0 to 15 (bit data : 0000 to 1111) 0 (bit data 0000) 40419 do2 output logic operation and 0000 to 00ff 0000 40421 do2 output logic operation or 0000 to 00ff 0000 40422 do2 scaling base -100.0 to 100.0% 0.0 40423 do2 scaling span -100.0 to 100.0% 100.0 40424 do2 proportion cycle 1 to 120 sec. 30 40425 do2 lower limits 0.0 to 100.0% 0 40426 do2 upper limits 0.0 to 100.0% 100.0 40427 do2 limit type 0 to 3 0 40428 do3 output type 0: event output 1: control output 0 (event output) 40429 do3 master module st. no. 0 to 255 0 40430 do3 master module ch. no. 1 to 4 1 40431 do3 bit position 0000 to 00ff 0004 40432 do3 output option 0 to 15 (bit data : 0000 to 1111) 0 (bit data 0000) 40433 do3 output logic operation and 0000 to 00ff 0000 40435 do3 output logic operation or 0000 to 00ff 0000 40436 do3 scaling base -100.0 to 100.0% 0.0 40437 do3 scaling span -100.0 to 100.0% 100.0 40438 do3 proportion cycle 1 to 120 sec. 30 40439 do3 lower limits 0.0 to 100.0% 0.0 40440 do3 upper limits 0.0 to 100.0% 100.0 40441 do3 limit type 0 to 3 0 40442 do4 output type 0: event output 1: control output 0 (event output) 40443 do4 master module st. no. 0 to 255 0 40444 do4 master module ch. no. 1 to 4 1 40445 do4 bit position 0000 to 00ff 0008 40446 do4 output option 0 to 15 (bit data : 0000 to 1111) 0 (bit data 0000) 40447 do4 output logic operation and 0000 to 00ff 0000 40449 do4 output logic operation or 0000 to 00ff 0000 40450 do4 scaling base -100.0 to 100.0% 0.0 40451 do4 scaling span -100.0 to 100.0% 100.0 40452 do4 proportion cycle 1 to 120 sec. 30 40453 do4 lower limits 0.0 to 100.0% 0.0 40454 do4 upper limits 0.0 to 100.0% 100.0 40455 do4 limit type 0 to 3 0 40456
pume 10 do parameter parameter (name) read/write date setting range factory default registor no. do5 output type 0: event output 1: control output 0 (event output) 40457 do5 master module st. no. 0 to 255 0 40458 do5 master module ch. no. 1 to 4 1 40459 do5 bit position 0000 to 00ff 0010 40460 do5 output option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0 0 0 0 ) 40461 do5 output logic operation and 0000 to 00ff 0000 40463 do5 output logic operation or 0000 to 00ff 0000 40464 do5 scaling base -100.0 to 100.0% 0.0 40465 do5 scaling span -100.0 to 100.0% 100.0 40466 do5 proportion cycle 1 to 120 sec. 30 40467 do5 lower limits 0.0 to 100.0% 0.0 40468 do5 upper limits 0.0 to 100.0% 100.0 40469 do5 limit type 0 to 3 0 40470 do6 output type 0: event output 1: control output 0 (event output) 40471 do6 master module st. no. 0 to 255 0 40472 do6 master module ch. no. 1 to 4 1 40473 do6 bit position 0000 to 00ff 0000 40474 do6 output option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0 0 0 0 ) 40475 do6 output logic operation and 0000 to 00ff 0000 40477 do6 output logic operation or 0000 to 00ff 0000 40478 do6 scaling base -100.0 to 100.0% 0.0 40479 do6 scaling span -100.0 to 100.0% 100.0 40480 do6 proportion cycle 1 to 120 sec. 30 40481 do6 lower limits 0.0 to 100.0% 0.0 40482 do6 upper limits 0.0 to 100.0% 100.0 40483 do6 limit type 0 to 3 0 40484 do7 output type 0: event output 1: control output 0 (event output) 40485 do7 master module st. no. 0 to 255 0 40486 do7 master module ch. no. 1 to 4 1 40487 do7 bit position 0000 to 00ff 0000 40488 do7 output option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0 0 0 0 ) 40489 do7 output logic operation and 0000 to 00ff 0000 40491 do7 output logic operation or 0000 to 00ff 0000 40492 do7 scaling base -100.0 to 100.0% 0.0 40493 do7 scaling span -100.0 to 100.0% 100.0 40494 do7 proportion cycle 1 to 120 sec. 30 40495 do7 lower limits 0.0 to 100.0% 0.0 40496 do7 upper limits 0.0 to 100.0% 100.0 40497 do7 limit type 0 to 3 0 40498 do8 output type 0: event output 1: control output 0 (event output) 40499 do8 master module st. no. 0 to 255 0 40500 do8 master module ch. no. 1 to 4 1 40501 do8 bit position 0000 to 00ff 0000 40502 do8 output option 0 to 15 (bit data : 0000 to 1111 ) 0 ( b i t d a t a 0 0 0 0 ) 40503 do8 output logic operation and 0000 to 00ff 0000 40505 do8 output logic operation or 0000 to 00ff 0000 40506 do8 scaling base -100.0 to 100.0% 0.0 40507 do8 scaling span -100.0 to 100.0% 100.0 40508 do8 proportion cycle 1 to 120 sec. 30 40509 do8 lower limits 0.0 to 100.0% 0.0 40510 do8 upper limits 0.0 to 100.0% 100.0 40511 do8 limit type 0 to 3 0 40512
11 internal do data area parameter parameter (name) read/write date setting range factory default registor no. internal do data area 1 event output 1: on 0: off control output 0.00 to 100.00 0 41001 internal do data area 2 0 41002 internal do data area 3 0 41003 internal do data area 4 0 41004 internal do data area 5 0 41005 internal do data area 6 0 41006 internal do data area 7 0 41007 internal do data area 8 0 41008 internal do data area 9 0 41009 internal do data area 10 0 4 1010 internal do data area 11 0 41011 internal do data area 12 0 41012 internal do data area 13 0 41013 internal do data area 14 0 41014 internal do data area 15 0 41015 internal do data area 16 0 41016 monitor parameter parameter (name) read/write date setting range factory default registor no. system fault status 0000 to ffff - 30064 do calculated result monitor 0000 to ffff - 31002 di calculated result monitor 0000 to ffff - 31001 di terminal monitor 0000 to ffff - 31003
pume printed in japan caution on safety *before using this product, be sure to read its instruction manual in advance. international sales div sales group gate city ohsaki, east tower, 11-2, osaki 1-chome, shinagawa-ku, tokyo 141-0032, japan http://www.fujielectric.com phone: 81-3-5435-7280, 7281 fax: 81-3-5435-7425 http://www.fjielectric.com/products/instruments/ information in this catalog is subject to change without notice.


▲Up To Search▲   

 
Price & Availability of EDS11-167A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X